| General specifications |
| Switching function |
Normally closed (NC) |
| Output type |
NAMUR |
| Rated operating distance |
2 mm |
| Installation |
flush |
| Assured operating distance |
0 ... 1.62 mm |
| Actual operating distance |
1.8 ... 2.2 mm typ. |
| Reduction factor rAl |
0.23 |
| Reduction factor rCu |
0.21 |
| Reduction factor r304 |
0.7 |
| Output type |
2-wire |
| Nominal ratings |
| Nominal voltage |
8.2 V (Ri approx. 1 kΩ) |
| Operating voltage |
5 ... 25 V |
| Switching frequency |
0 ... 1000 Hz |
| Hysteresis |
1 ... 10 typ. 5 % |
| Reverse polarity protection |
reverse polarity protected |
| Short-circuit protection |
yes |
| Suitable for 2:1 technology |
yes , Reverse polarity protection diode not required |
| Current consumption |
|
|
Measuring plate not detected |
≥ 2.2 mA at nominal voltage |
|
Measuring plate detected |
≤ 1 mA at nominal voltage |
| Switching state indicator |
Multihole-LED, yellow |
| Functional safety related parameters |
| MTTFd |
2099 a |
| Mission Time (TM) |
20 a |
| Diagnostic Coverage (DC) |
0 % |
| Compliance with standards and directives |
| Standard conformity |
|
|
NAMUR |
EN 60947-5-6:2000
IEC 60947-5-6:1999 |
|
Electromagnetic compatibility |
NE 21:2007 |
|
Standards |
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
| Approvals and certificates |
| IECEx approval |
|
|
Equipment protection level Ga |
IECEx PTB 11.0037X |
|
Equipment protection level Gb |
IECEx PTB 11.0037X |
|
Equipment protection level Da |
IECEx PTB 11.0037X |
|
Equipment protection level Mb |
IECEx PTB 11.0037X |
| ATEX approval |
|
|
Equipment protection level Ga |
PTB 00 ATEX 2048 X |
|
Equipment protection level Gb |
PTB 00 ATEX 2048 X |
|
Equipment protection level Gc (ic) |
PF13CERT2895 X |
|
Equipment protection level Da |
PTB 00 ATEX 2048 X |
| EAC conformity |
TR CU 012/2011 |
| FM approval |
|
|
Control drawing |
116-0165 |
| UL approval |
|
|
Ordinary Location |
E87056 |
|
Hazardous Location |
E501628 |
|
Control drawing |
116-0452 |
| CSA approval |
cCSAus Listed, General Purpose |
| CCC approval |
|
|
Hazardous Location |
2020322315002255 |
| NEPSI approval |
|
|
NEPSI certificate |
GYJ16.1393X |
| Marine approval |
DNVGL TAA00001A5 |
| Ambient conditions |
| Ambient temperature |
-25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature |
-40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
| Connection type |
Connector plug M12 x 1 , 4-pin |
| Housing material |
Stainless steel 1.4305 / AISI 303 |
| Sensing face |
PBT |
| Degree of protection |
IP66 / IP67 |
| General information |
| Scope of delivery |
2 self locking nuts in scope of delivery |
| Use in the hazardous area |
see instruction manuals |