General specifications |
Switching function |
Normally closed (NC) |
Output type |
NAMUR |
Rated operating distance |
2 mm |
Installation |
flush |
Assured operating distance |
0 ... 1.62 mm |
Actual operating distance |
1.8 ... 2.2 mm typ. |
Reduction factor rAl |
0.23 |
Reduction factor rCu |
0.21 |
Reduction factor r304 |
0.7 |
Output type |
2-wire |
Nominal ratings |
Nominal voltage |
8.2 V (Ri approx. 1 kΩ) |
Switching frequency |
0 ... 1000 Hz |
Hysteresis |
1 ... 10 typ. 3 % |
Reverse polarity protection |
reverse polarity protected |
Short-circuit protection |
yes |
Suitable for 2:1 technology |
yes , Reverse polarity protection diode not required |
Current consumption |
|
|
Measuring plate not detected |
min. 3 mA |
|
Measuring plate detected |
≤ 1 mA |
Switching state indicator |
all direction LED, yellow |
Functional safety related parameters |
MTTFd |
2099 a |
Mission Time (TM) |
20 a |
Diagnostic Coverage (DC) |
0 % |
Compliance with standards and directives |
Standard conformity |
|
|
NAMUR |
EN 60947-5-6:2000
IEC 60947-5-6:1999 |
|
Electromagnetic compatibility |
NE 21:2007 |
|
Standards |
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
IECEx approval |
|
|
Equipment protection level Ga |
IECEx PTB 11.0037X |
|
Equipment protection level Gb |
IECEx PTB 11.0037X |
|
Equipment protection level Da |
IECEx PTB 11.0037X |
|
Equipment protection level Mb |
IECEx PTB 11.0037X |
ATEX approval |
|
|
Equipment protection level Ga |
PTB 00 ATEX 2048 X |
|
Equipment protection level Gb |
PTB 00 ATEX 2048 X |
|
Equipment protection level Gc (ic) |
PF13CERT2895 X |
|
Equipment protection level Da |
PTB 00 ATEX 2048 X |
|
Equipment protection level Dc (tc) |
PF15CERT3774X |
EAC conformity |
TR CU 012/2011 |
FM approval |
|
|
Control drawing |
116-0165 |
UL approval |
|
|
Ordinary Location |
E87056 |
|
Hazardous Location |
E501628 |
|
Control drawing |
116-0452 |
CSA approval |
cCSAus Listed, General Purpose |
CCC approval |
|
|
Hazardous Location |
2020322315002255 |
NEPSI approval |
|
|
NEPSI certificate |
GYJ16.1393X |
Ambient conditions |
Ambient temperature |
-25 ... 100 °C (-13 ... 212 °F) |
Storage temperature |
-40 ... 100 °C (-40 ... 212 °F) |
Mechanical specifications |
Connection type |
cable PVC , 2 m |
Core cross-section |
0.34 mm2 |
Housing material |
Stainless steel 1.4305 / AISI 303 |
Sensing face |
PBT |
Degree of protection |
IP66 / IP67 |
Cable |
|
|
Cable diameter |
4.6 mm ± 0.2 mm |
|
Bending radius |
> 12 x cable diameter |
General information |
Scope of delivery |
2 self locking nuts in scope of delivery |
Use in the hazardous area |
see instruction manuals |