General specifications |
Switching function |
Normally open (NO) |
Output type |
NAMUR with safety function |
Rated operating distance |
6 mm |
Installation |
flush |
Assured operating distance |
0 ... 4.86 mm |
Reduction factor rAl |
1 |
Reduction factor rCu |
1 |
Reduction factor r304 |
0 |
Output type |
2-wire |
Nominal ratings |
Nominal voltage |
8.2 V (Ri approx. 1 kΩ) |
Switching frequency |
0 ... 100 Hz |
Current consumption |
|
|
Measuring plate not detected |
≤ 1 mA |
|
Measuring plate detected |
≥ 3 mA |
Functional safety related parameters |
Safety Integrity Level (SIL) |
SIL 3 |
MTTFd |
9191 a |
Mission Time (TM) |
20 a |
Diagnostic Coverage (DC) |
0 % |
Compliance with standards and directives |
Standard conformity |
|
|
NAMUR |
EN 60947-5-6:2000
IEC 60947-5-6:1999 |
|
Standards |
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
IECEx approval |
|
|
Equipment protection level Ga |
IECEx PTB 11.0092X |
|
Equipment protection level Gb |
IECEx PTB 11.0092X |
|
Equipment protection level Da |
IECEx PTB 11.0092X |
|
Equipment protection level Mb |
IECEx PTB 11.0092X |
ATEX approval |
|
|
Equipment protection level Ga |
PTB 00 ATEX 2049 X |
|
Equipment protection level Gb |
PTB 00 ATEX 2049 X |
|
Equipment protection level Da |
PTB 00 ATEX 2049 X |
FM approval |
|
|
Control drawing |
116-0165 |
UL approval |
cULus Listed, General Purpose |
|
Ordinary Location |
E87056 |
|
Hazardous Location |
E501628 |
|
Control drawing |
116-0454 |
CSA approval |
cCSAus Listed, General Purpose |
CCC approval |
|
|
Hazardous Location |
2020322315002281 |
NEPSI approval |
|
|
NEPSI certificate |
GYJ16.1392X |
Ambient conditions |
Ambient temperature |
-25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications |
Connection type |
screw terminals |
Information for connection |
A maximum of two conductors with the same core cross section may be mounted on one terminal connection!
tightening torque 1.2 Nm + 10 % |
Core cross-section |
up to 2.5 mm2 , stripped insulation length: 7 mm |
|
Minimum core cross-section |
without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 |
|
Maximum core cross-section |
without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 |
Connection (system side) |
screw terminals , M20 x 1.5 cable gland , usable thread length 9.1 mm , screw-in depth max. 9.1 mm |
Housing material |
PBT |
Sensing face |
PBT |
Degree of protection |
IP68 |
Note |
only for non-ferrous metal |
General information |
Use in the hazardous area |
see instruction manuals |