| General specifications |
| Switching function |
Normally open (NO) |
| Output type |
NPN |
| Rated operating distance |
40 mm |
| Installation |
non-flush |
| Output polarity |
DC |
| Assured operating distance |
0 ... 32.4 mm |
| Actual operating distance |
36 ... 44 mm typ. 40 mm |
| Reduction factor rAl |
0.5 |
| Reduction factor rCu |
0.45 |
| Reduction factor r304 |
0.8 |
| Output type |
3-wire |
| Nominal ratings |
| Operating voltage |
10 ... 60 V |
| Switching frequency |
0 ... 100 Hz |
| Hysteresis |
1 ... 10 typ. 5 % |
| Reverse polarity protection |
reverse polarity protected |
| Short-circuit protection |
pulsing |
| Voltage drop |
≤ 2.8 V |
| Voltage drop at IL |
|
|
Voltage drop IL = 1 mA, switching element on |
0.5 ... 2.3 V typ. 0.9 V |
|
Voltage drop IL = 10 mA, switching element on |
0.8 ... 2.2 V typ. 1.4 V |
|
Voltage drop IL = 20 mA, switching element on |
0.9 ... 2.3 V typ. 1.5 V |
|
Voltage drop IL = 50 mA, switching element on |
0.9 ... 2.5 V typ. 1.6 V |
|
Voltage drop IL = 100 mA, switching element on |
1 ... 2.6 V typ. 1.8 V |
|
Voltage drop IL = 200 mA, switching element on |
1.2 ... 2.8 V typ. 2 V |
| Operating current |
0 ... 200 mA |
| Off-state current |
0 ... 0.5 mA typ. 0.01 mA |
|
Off-state current TU =40 °C, switching element off |
≤ 100 µA |
| No-load supply current |
≤ 10 mA |
| Time delay before availability |
≤ 100 ms |
| Operating voltage indicator |
LED, green |
| Switching state indicator |
LED, yellow |
| Compliance with standards and directives |
| Standard conformity |
|
|
Standards |
EN 60947-5-2:2007
IEC 60947-5-2:2007 |
| Approvals and certificates |
| UL approval |
cULus Listed, General Purpose |
| CSA approval |
cCSAus Listed, General Purpose |
| CCC approval |
Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
| Ambient temperature |
-25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature |
-25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
| Connection type |
screw terminals |
| Information for connection |
A maximum of two conductors with the same core cross section may be mounted on one terminal connection!
tightening torque 1.2 Nm + 10 % |
| Core cross-section |
up to 2.5 mm2 |
|
Minimum core cross-section |
without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 |
|
Maximum core cross-section |
without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 |
| Housing material |
PBT |
| Sensing face |
PBT |
| Degree of protection |