Communication |
Modbus (TCP, UDP); ETHERNET; EtherNet/IPTM Adapter (slave), library for e!RUNTIME; Modbus® RTU; RS-232 serial interface; RS-485 interface; MQTT; EtherCAT® master (requires an additional license); BACnet/IP, requires an additional license |
ETHERNET protocols |
DHCP; DNS; NTP; FTP; FTPS; SNMP; HTTP; HTTPS; SSH |
Visualization |
Web-Visu |
Operating system |
Real-time Linux (with RT-Preempt patch) |
CPU |
Cortex A8; 1 GHz |
Programming languages per IEC 61131-3 |
Instruction List (IL); Ladder Diagram (LD); Function Block Diagram (FBD), Continuous Function Chart (CFC); Structured Text (ST); Sequential Function Chart (SFC); |
Programming environment |
e!COCKPIT (based on CODESYS V3); WAGO-I/O-PRO V2.3 (based on CODESYS V2.3) |
Configuration options |
e!COCKPIT; WAGO-I/O-CHECK; Web-Based Management; e!RUNTIME Library; CODESYS Library |
Baud rate (communication/fieldbus 1) |
10/100 Mbit/s |
Baud rate |
ETHERNET: 10/100 Mbit/s |
Transmission medium (communication/fieldbus) |
ETHERNET: Twisted Pair S-UTP; 100 Ω; Cat. 5; M12 D-coded; 100 m maximum cable length |
Main memory (RAM) |
512MB |
Internal memory (flash) |
4096MB |
Non-volatile hardware memory |
128 |
Program memory |
CODESYS V2: 16 MB; e!RUNTIME: 32 MB |
Data memory |
CODESYS V2: 64 MB; e!RUNTIME: 128 MB |
Non-volatile software memory |
128 |
Non-volatile software memory |
128. |
Type of memory card |
SD and SDHC up to 32 GB (all guaranteed properties only valid with WAGO Memory Card) |
Memory card slot |
Push-push mechanism; Cover lid (sealable) |
Number of modules per node (max.) |
64 |
Input and output process image (internal) max. |
1000 words/1000 words |
Input and output process image (Modbus®) max. |
CODESYS V2: 1000 words/1000 words; e!RUNTIME: 32000 words/32000 words |
Indicators |
LED (SYS, RUN, I/O, U1 … U7) red/green/orange: Status of system, program, local data bus, status programmable by user (can be used via CODESYS library); LED (A, C) green: Status of system power supply, field supply |
Derating |
Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple) |
Supply voltage (system) |
24 VDC; via pluggable connector (CAGE CLAMP® connection); Derating must be observed! |
Input current (typ.) at nominal load (24 V) |
550mA |
Total current (system supply) |
1,700mA |
Supply voltage (field) |
24 VDC; Power supply via pluggable connector (CAGE CLAMP® connection); Transmission via power jumper contacts; Derating must be observed! |
Current carrying capacity (power jumper contacts) |
10A |
Number of outgoing power jumper contacts |
2 |
Rated surge voltage |
1 kV |