General specifications |
Switching function |
Normally closed (NC) |
Output type |
NAMUR |
Rated operating distance |
20 mm |
Installation |
flush |
Assured operating distance |
0 ... 16.2 mm |
Actual operating distance |
18 ... 22 mm |
Reduction factor rAl |
0.37 |
Reduction factor rCu |
0.35 |
Reduction factor r304 |
0.79 |
Output type |
2-wire |
Nominal ratings |
Nominal voltage |
8.2 V (Ri approx. 1 kΩ) |
Switching frequency |
0 ... 250 Hz |
Hysteresis |
1 ... 15 typ. 5 % |
Reverse polarity protection |
reverse polarity protected |
Short-circuit protection |
yes |
Current consumption |
|
|
Measuring plate not detected |
≥ 3 mA |
|
Measuring plate detected |
≤ 1 mA |
Switching state indicator |
LED, yellow |
Functional safety related parameters |
MTTFd |
1697 a |
Mission Time (TM) |
20 a |
Diagnostic Coverage (DC) |
0 % |
Compliance with standards and directives |
Standard conformity |
|
|
NAMUR |
EN 60947-5-6:2000
IEC 60947-5-6:1999 |
|
Electromagnetic compatibility |
NE 21:2007 |
|
Standards |
EN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
IECEx approval |
|
|
Equipment protection level Ga |
IECEx PTB 11.0021X |
|
Equipment protection level Gb |
IECEx PTB 11.0021X |
|
Equipment protection level Da |
IECEx PTB 11.0021X |
|
Equipment protection level Mb |
IECEx PTB 11.0021X |
ATEX approval |
|
|
Equipment protection level Ga |
PTB 00 ATEX 2032 X |
|
Equipment protection level Gb |
PTB 00 ATEX 2032 X |
|
Equipment protection level Gc (ic) |
PF13CERT2895 X |
|
Equipment protection level Da |
PTB 00 ATEX 2032 X |
EAC conformity |
TR CU 012/2011 |
UL approval |
cULus Listed, General Purpose |
|
Ordinary Location |
E87056 |
|
Hazardous Location |
E501628 |
|
Control drawing |
116-0451 |
CCC approval |
|
|
Hazardous Location |
2020322315002303 |
NEPSI approval |
|
|
NEPSI certificate |
GYJ16.1394X |
Marine approval |
DNVGL TAA00001A5 |
Ambient conditions |
Ambient temperature |
-25 ... 100 °C (-13 ... 212 °F) |
Storage temperature |
-40 ... 100 °C (-40 ... 212 °F) |
Mechanical specifications |
Connection type |
screw terminals |
Information for connection |
A maximum of two conductors with the same core cross section may be mounted on one terminal connection!
tightening torque 1.2 Nm + 10 % |
Core cross-section |
up to 2.5 mm2 , stripped insulation length: 7 mm |
|
Minimum core cross-section |
without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 |
|
Maximum core cross-section |
without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 |
Connection (system side) |
screw terminals , M20 x 1.5 cable gland , usable thread length 9.1 mm , screw-in depth max. 9.1 mm |
Housing material |
PA |
Sensing face |
PA |
Degree of protection |
IP66 / IP68 / IP69K |
Mass |
225 g |
Note |
Tightening torque: 1.8 Nm (housing) |
General information |
Use in the hazardous area |
see instruction manuals |